Chiller Water Flow Formula:
| From: | To: |
The chiller water flow rate represents the volume of water circulating through a chiller system per minute, measured in gallons per minute (GPM). It is a critical parameter for proper chiller operation and efficiency.
The calculator uses the chiller water flow formula:
Where:
Explanation: The formula calculates the required water flow based on chiller capacity and the temperature difference between supply and return water.
Details: Proper flow rate ensures efficient heat transfer, prevents chiller damage, maintains system performance, and optimizes energy consumption in HVAC systems.
Tips: Enter chiller capacity in tons and temperature difference in °F. Both values must be positive numbers for accurate calculation.
Q1: What is the significance of the 2.4 constant?
A: The constant 2.4 converts tons of refrigeration to GPM, accounting for the specific heat of water and unit conversions.
Q2: What is a typical ΔT for chiller systems?
A: Typical ΔT ranges from 10°F to 12°F for efficient operation, though it can vary based on system design and application.
Q3: How does flow rate affect chiller efficiency?
A: Too low flow can cause freezing, while too high flow increases pump energy and may reduce heat transfer efficiency.
Q4: Can this formula be used for all chiller types?
A: This formula is primarily for water-cooled chillers. Air-cooled and other chiller types may have different calculation methods.
Q5: What units should be used for accurate results?
A: Use tons for capacity and °F for temperature difference to get flow rate in GPM. For metric units, different conversion factors apply.